Nota importante: Filter start-up
The filter must be installed before the softener (if present), or in any case immediately after the meter. After installation, the filter must be rinsed with running water. Before washing the filter, open the drain valve and make sure it terminates in a container lwide enough to collect the drain water. Pay ATTENTION to the water pressure.
The filter must be installed before the softener (if present), or in any case immediately after the meter. After installation, the filter must be rinsed with running water. Before washing the filter, open the drain valve and make sure it terminates in a container lwide enough to collect the drain water. Pay ATTENTION to the water pressure.
Istruzioni d'uso: Routine maintenance
MY/AT1M12 filter with one pressure gauge: it must be cleaned when the pressure indicated by the pressure gauge is approximately 1 bar.
MY/AT2M34 filter with two pressure gauges: it must be cleaned when the pressure drop is approximately 1.5 bar.
MY/AT34 filter without pressure gauge: it must be cleaned in case of excess of turbidity and at least once a month.
Before washing the filter, make sure it terminates in a container wide enough to collect the drain water. Open the drain valve. The valve must be opened intermittently, once every 5/6 seconds, and quickly, considering the water pressure: in this way an efficient cleaning of the filter will be ensured without having to disassemble it.
Extraordinary maintenance
When the filter has not been cleaned for a long time, it may be necessary to disassemble it and thoroughly clean each component. This operation can be performed only by qualified professional operators.
MY/AT1M12 filter with one pressure gauge: it must be cleaned when the pressure indicated by the pressure gauge is approximately 1 bar.
MY/AT2M34 filter with two pressure gauges: it must be cleaned when the pressure drop is approximately 1.5 bar.
MY/AT34 filter without pressure gauge: it must be cleaned in case of excess of turbidity and at least once a month.
Before washing the filter, make sure it terminates in a container wide enough to collect the drain water. Open the drain valve. The valve must be opened intermittently, once every 5/6 seconds, and quickly, considering the water pressure: in this way an efficient cleaning of the filter will be ensured without having to disassemble it.
Extraordinary maintenance
When the filter has not been cleaned for a long time, it may be necessary to disassemble it and thoroughly clean each component. This operation can be performed only by qualified professional operators.